External battery pack compatibility
DC system voltage (VDC)
Battery recharge rate (included
batteries)
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Undervoltage correction
Severe undervoltage correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating
UPS AC suppression response time
EMI / RFI AC noise suppression
AC suppression joule rating
AC suppression response time
PHYSICAL
Installation form factors supported
with included accessories
Primary form factor
UPS / Power Module dimensions in
primary form factor (height x width x
depth / inches)
UPS / Power Module dimensions in
primary form factor (height x width x
depth / cm)
UPS / Power Module weight (lbs)
UPS / Power Module weight (kg)
UPS Shipping dimensions (height x
width x depth / inches)
BP24V28-2U (limit 1); BP24V70-3U (multi-pack compatible)
24
Less than 9 hours from 10% to 90%
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 87 to 140
Input voltages between 127 and 140 are reduced by 12%
Input voltages between 95 and 105 are boosted by 10%
Input voltages between 87 and 94 are boosted by 22%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation; set of 4 rear-panel switches control
system enable and contact closure port inverter shutoff commands
720
Instantaneous
Yes
720
Instantaneous
Tower
Tower
17 x 9 x 12.5
43.2 x 22.9 x 31.8
80
36.3
22.2 x 12.8 x 16.5
3 / 5